Chapter
4
Start-Up
Start-Up Procedures
This chapter guides you through a basic start-up of the drive using factory default
parameter settings. The objective is to verify power and control wiring, set motor
direction, control motor speed and prepare you for programming parameters
(tuning) if necessary. Refer to Chapter 5 for a complete listing and description of
parameters and programming information.
ATTENTION:
Power must be applied to the drive to perform the
following start-up procedure. Some of the voltages present are at
incoming line potential. To avoid electric shock hazard or damage to
equipment, only qualified service personnel should perform the
following procedure. Thoroughly read and understand the procedure
before beginning. If an event does not occur while performing this
procedure,
Do Not Proceed
.
Remove Power
by opening the branch
circuit disconnect device and correct the malfunction before
continuing.
ATTENTION:
A DC Bus voltage may be present at TB1 and TB2 for approximately
three minutes after power is removed from the drive.
Start-Up Checklist
Verify that the drive is installed per the instructions in Chapter 2, including…
• Drive is mounted on a flat, vertical and level surface.
• Minimum clearance distance between drive and other equipment.
• Proper grounding practices have been followed.
• Proper power and control wiring has been used.
• No external power applied to control inputs.
Verify that AC line power at the disconnect device is within the rated value of the drive.
IMPORTANT:
Verify that a closed contact input is present at TB3-8. See Chapter 2,
Control Wiring
for details
onTB3-8 functionality when using P46 - [Input Mode] settings 4 through 9.
Disconnect and lock out all incoming power to the drive including incoming
AC power to terminals R, S and T (L1, L2 and L3) of TB1.
Confirm that all other control inputs are connected to the correct terminals and are secure.
Verify that the motor leads are connected to the power terminal block TB2, terminals U, V, W (T1, T2, T3).
continued on next page
Remove debris label and reconnect power to drive.
Summary of Contents for Allen-Bradley 160 SSC Series
Page 12: ...1 6 Getting Started End of Chapter ...
Page 58: ...5 20 Parameters and Programming End of Chapter ...