Publication 1747-UM013B-EN-P - January 2005
M0 - M1 Files and G Files
B-5
SLC 5/02 Processor Example
If you are using a SLC 5/02 Series B processor, add 1930 µs to the
program scan time for each bit instruction addressed to an M0 or M1
data file. If you are using a SLC 5/03 Series C processor, add 1160 µs.
Processor
Instruction Type
Access Time per
Bit Instruction or
Word of Data
Access Time per
Multi-Word
Instruction
SLC 5.02 Series B
All Types
(1)
(1) Except the OSR instruction and the instruction parameters noted on page B-2.
1930 µs
1580 µs plus 670 µs
per word
SLC 5/02 Series C
All Types
(1)
1160 µs
950 µs plus 400 µs
per word
SLC 5/03 (All Times)
XIC or XIO
782 µs
- -
OTU, OTE, or OTL
925 µs
- -
COP to M file
- -
772 µs plus 23 µs
per word
COP from M file
- -
760 µs plus 22 µs
per word
FLL
- -
753 µs plus 30 µs
per word
MVM to M file
894 µs
- -
any source or
Destination M file
address
730 µs
- -
SLC 5/04 OS 400
SLC 5/05
XIC or XIO
743 µs
- -
OTU, OTE, or OTL
879 µs
- -
COP to M file
- -
735 µs plus 23 µs
per word
COP from M file
- -
722 µs plus 22 µs
per word
FLL
- -
716 µs plus 30 µs
per word
MVM to M file
850 µs
- -
any source or
Destination M file
address
694 µs
- -
] [
M0:2.1
1
]/[
M1:3.1
1
( )
M0:2.1
10