Publication 1747-UM013B-EN-P - January 2005
D-18
Block Transfer Examples for Earlier Processors
Rung 2:5
WHEN A BTR SUCCESSFULLY COMPLETES, BUFFER THE BTR DATA AND UNLATCH BOTH THE
BTR VIRTUAL ENABLE BIT AND THE BTR PENDING BIT. ALSO, LATCH THE BIT THAT
CONTINUES CHECKING THE BTR STATUS UNTIL THE SN MODULE TURNS OFF THE DONE BIT.
| |
| |
| VIRTUAL |
| BTR DONE |
| BIT BTR DATA |
| N7:60 +COP---------------+ |
|----] [----------------------------------------------+-+COPY FILE +-+-|
| 13 | |Source #M1:1.110| | |
| | |Dest #N7:0| | |
| | |Length 10| | |
| | +------------------+ | |
| | | |
| | | |
| | | |
| | BTR | |
| | PENDING | |
| | B3 | |
| +----(U)---------------+ |
| | 0 | |
| | | |
| | | |
| | VIRTUAL | |
| | BTR ENABLE | |
| | BIT | |
| | N7:50 | |
| +----(U)---------------+ |
| | 15 | |
| | | |
|
| | |
| | | |
| | | |
| | | |
| | CHECK BTR | |
| | STATUS | |
| | B3 | |
| +----(L)---------------+ |
| 2 |
Rung 2:6
WHEN A BTR UNSUCCESSFULLY COMPLETES, BUFFER THE ERROR CODE AND UNLATCH THE BTR
ENABLE BIT AND THE BTR PENDING BIT. ALSO, LATCH THE CHECK BTR STATUS BIT IN
ORDER TO CONTINUE READING THE STATUS INFORMATION FROM THE SCANNER UNTIL IT
TURNS OFF THE ERROR BIT, COMPLETING THE HAND-SHAKE PROCESS.
| |
| |
| VIRTUAL |
| BTR ERROR BTR ERROR |
| BIT CODE |
| N7:60 +MOV---------------+ |
|----] [----------------------------------------------+-+MOVE +-+-|
| 12 | |Source M1:1.103| | |
| | | *| | |
| | |Dest N7:0| | |
| | | 0| | |
| | +------------------+ | |
| | | |
| | | |
| | | |
| | BTR | |
| | PENDING | |
| | B3 | |
| +----(U)---------------+ |
| | 0 | |
| | | |
| | | |
| | VIRTUAL | |
| | BTR ENABLE | |
| | BIT | |
| | N7:50 | |
| +----(U)---------------+ |
| | 15 | |
| | | |
| | | |
| | | |
| | CHECK BTR | |
| | STATUS | |
| | B3 | |
| +----(L)---------------+ |
| 2 |
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com