Chapter 7
Configure your Digital Module on an EtherNet/IP Network
Using RSLinx software to set the IP Address
To use RSLinx to configure the EtherNet/IP module:
1.
Make sure that the module is installed and powered up.
2.
Start RSLinx. The RSWho window opens. Navigate in RSWho to the
Ethernet network.
3.
Right-click on the EtherNet/IP module (not the controller, if there is one)
and select Module Configuration.
4.
Select the Port Configuration tab, choose Status Network Configuration
type, and enter the IP address and the other network parameters, if needed.
5.
Also, select the Static radio button to permanently assign this
configuration to the port. If you select Dynamic, on a power cycle, the
controller clears the current IP configuration and will again begin sending
BOOTP requests.