Configure Your Adapter and Digital Modules on a ControlNet Network
Chapter
6
Notice that the 1756-CNB Bridge is now on line, but the rest of the I/O
configuration (adapter and I/O modules) connections are not scheduled (notice
the yellow triangles).
Configure the 1794-ACN15
Adapter
You have now built the I/O tree in RSLogix 5000, and the RSLogix 5000
software used the chassis size from the 1794-ACN15 General Tab. Now you
must download this new chassis size value into the 1794-ACN15 adapter
hardware. This procedure will synchronize the chassis size value from the
RSLogix 5000 software into the 1794-ACN15 adapter.
1.
Highlight the 1794-ACN15 adapter, and right-click to choose
Properties
.
Verify the node address and the chassis size.