Rockwell Automation Publication 1794-UM061B-EN-P - March 2020
Chapter 6
Configure Your Adapter and Digital Modules on a ControlNet Network
2.
Click the
Connection
tab.
Notice that the connection request error is still present because we haven’t
scheduled any of the I/O module connections yet. You do that through
RSNetWorx for ControlNet.
Schedule I/O Module
Connections
Use these procedures to schedule I/O module connections.
1.
Start RSNetWorx for ControlNet.
2.
From the
File
menu, choose
New
.
3.
Click
OK
.
4.
Choose
Network>Online
.