32
Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
Chapter 2
Planning the Kinetix 5500 Drive System Installation
Standalone Drive Systems
Table 6 - Fuse Selection (Bussmann part numbers)
Table 7 - Circuit Breaker Selection (Allen-Bradley catalog numbers)
Shared DC (common-bus) Drive Systems
Table 8 - Fuse Selection (Bussmann part numbers)
Table 9 - Circuit Breaker Selection (Allen-Bradley catalog numbers)
Kinetix 5500 Drive Cat. No.
Three-phase
Single-phase
2198-H003-ERS
x
KTK-R-3
KTK-R-2
2198-H008-ERS
x
KTK-R-7
KTK-R-5
2198-H015-ERS
x
KTK-R-15
KTK-R-10
2198-H025-ERS
x
KTK-R-20
N/A
2198-H040-ERS
x
KTK-R-25
2198-H070-ERS
x
LPJ-35SP
Kinetix 5500 Drive Cat. No.
Three-phase
(1)
(1) UL has not approved circuit breakers for use as branch circuit protection for Kinetix 5500 drive systems.
Single-phase
2198-H003-ERS
x
140U-D6D3-B20
140U-D6D2-B10
2198-H008-ERS
x
140U-D6D3-B60
140U-D6D2-B20
2198-H015-ERS
x
140U-D6D3-C12
140U-D6D2-B80
2198-H025-ERS
x
140U-D6D3-C20
N/A
2198-H040-ERS
x
140U-D6D3-C25
2198-H070-ERS
x
N/A
Kinetix 5500 Drive Cat. No.
Three-phase
2198-H003-ERS
x
KTK-R-10
2198-H008-ERS
x
2198-H015-ERS
x
KTK-R-15
2198-H025-ERS
x
KTK-R-20
2198-H040-ERS
x
KTK-R-25
2198-H070-ERS
x
LPJ-35SP
Kinetix 5500 Drive Cat. No.
Three-phase
(1)
(1) UL has not approved circuit breakers for use as branch circuit protection for Kinetix 5500 drive systems.
2198-H003-ERS
x
N/A
2198-H008-ERS
x
2198-H015-ERS
x
140U-D6D3-C15
2198-H025-ERS
x
140U-D6D3-C20
2198-H040-ERS
x
140U-D6D3-C25
2198-H070-ERS
x
N/A