Chapter 3
Mounting the Kinetix 5500 Drive System
Single-axis Configurations
The following restrictions exist for standalone (single-axis) configurations:
•
Standalone (single-axis) drives can be mounted to the panel individually or
by using the zero-stack tab and cutout (refer to
)
•
The shared-bus connection system does not apply and must not be used
For a single-axis example configuration, refer to
Typical Kinetix 5500 Standalone
.
Multi-axis Configurations
Each multi-axis configuration has restrictions that apply:
•
The shared-bus connection system must be used. Do not attach discrete
wires from drive-to-drive.
•
The maximum number of drives in Shared AC bus power-sharing groups
cannot exceed 5.
•
The maximum number of drives in any other bus power-sharing group
cannot exceed 8.
For a multi-axis example configuration, refer to
.