Advanced Program Group
(continued)
A113 [Anlg In4-20mA Hi]
Related Parameter(s):
,
Sets the analog input level that corresponds to
[Maximum Freq] if a 4-20mA input is used by
[Speed Reference].
Analog inversion can be accomplished by setting this value smaller than A112 [Anlg In4-20mA Lo].
Values
Default:
100.0%
Min/Max:
0.0/100.0%
Display:
0.1%
A114 [Slip Hertz @ FLA]
Related Parameter(s):
Compensates for the inherent slip in an induction motor. This frequency is added to the commanded
output frequency based on motor current.
Values
Default:
2.0 Hz
Min/Max:
0.0/10.0 Hz
Display:
0.1 Hz
A115 [Process Time Lo]
Related Parameter(s):
,
Scales the time value when the drive is running at
[Minimum Freq]. When set to a value other
than zero,
[Process Display] indicates the duration of the process.
Values
Default:
0.00
Min/Max:
0.00/99.99
Display:
0.01
A116 [Process Time Hi]
Related Parameter(s):
,
Scales the time value when the drive is running at
[Maximum Freq]. When set to a value other
than zero,
[Process Display] indicates the duration of the process.
Values
Default:
0.00
Min/Max:
0.00/99.99
Display:
0.01
A117 [Bus Reg Mode]
Controls the operation of the drive voltage regulation, which is normally operational at decel or when
the bus voltage rises.
Refer to the Attention statement on page
for important information on bus regulation.
Options
0 “Disabled”
1 “Enabled” (Default)
A118 [Current Limit 2]
,
,
Maximum output current allowed before current limiting occurs. This parameter is only active if
[Digital Inx Sel] is set to 25 “Current Lmt2” and is active.
Values
Default:
Drive Rated Amps
×
1.5
Min/Max:
0.1/(Drive Rated Amps
×
1.8)