Industrial Integrated Display Computers
3
Publication 6181P-IN010C-EN-P - December 2009
Environment and Enclosure Information
Review the information on enclosures and environments before installing the product.
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes
up to 2000 m (6561 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR Publication 11. Without appropriate precautions, there may be potential
difficulties ensuring electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.
UL listed equipment need not be mounted inside another enclosure if NEMA Type and IEC
ratings are not required, but the mounting method must limit the tilt of the product to
±60° from vertical. An example is a tabletop stand. The mounting means must be firmly
attached to the supporting surface using screws, bolts, or clamps so the computer cannot
tip. These units ship with a gasketed bezel to meet specified NEMA and IEC ratings only
when mounted in a panel or enclosure with an equivalent rating. Subsequent sections of
this publication may contain additional information regarding specific enclosure type
ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
•
1770-4.1
.
•
NEMA Standards publication 250 and IEC publication 60529, as applicable, for
explanations of the degrees of protection provided by different types of enclosure.