Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation
3-49
Figure 3.95 — CT Position for Single-Phase Heaters
Three-phase Heaters
When a 3-phase power supply is used, regardless of the types of connecting
lines, two current transformers (CTs) are required to detect heater burnout and
HS.
1. For Delta connecting power lines:
Refer to the following diagram for
CT installation positions.
Note:
Heater voltage fluctuations are not considered here. Take this into
account when setting the detection current.
Figure 3.96 — CT Installation Positions, Delta Connecting Power Lines
2. For Star (Y) connecting power lines:
Refer to the following diagram
for CT installation positions.
Note:
Heater voltage fluctuations are not considered here. Take this into
account when setting the detection current.
Figure 3.97 — CT Installation Positions, Start (Y) Connection Power Lines
CT
Load
Load (such as a heater)
AC line
To controller
CT input
CT
Load
Load
To controller CT input
Load
Load (such as a heater)
AC line
AC line
To controller CT input
CT
CT
Load
Load
Load
Load (such as a heater)
AC line
To controller CT input
To controller CT input
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...