Publication 900-UM007D-EN-E - January 2011
3-58
Configuration & Basic Operation
HS Alarm Setup
To activate the HS alarm, set the HS Alarm Use parameter to ON in the
Advanced Setting function group and set the HS Alarm 1 and HS Alarm 2
parameters in the Adjustment function group.
EXAMPLE
Operating Procedure: Moving to the Advanced Setting Function Group
The HS Alarm Use parameter setting is already ON by default, so set the HS
Alarm 1 parameter to 2.5.
1.
Move to the Advanced Setting function group.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 3.116
2.
Select Move to Advanced Setting function group by pressing the
M
key.
Figure 3.117
3.
Press the
D
key to enter the password (
−
169
), and move from the
Initial Setting function group to the Advanced Setting function group.
The top parameter in the Advanced Setting function group is displayed.
Figure 3.118
4.
Select the HS Alarm Use parameter by pressing the
M
key.
Check that this parameter is set to ON (the default).
Next, set the Leakage Current 1 Monitor parameter.
Figure 3.119
C
25
100
PV/SP
in-t
5
Input type
init
off
amov
-169
Moves to Advanced
Setting Function Group
hsu
on
HS alarm
use
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...