Publication 900-UM007D-EN-E - January 2011
4-16
Parameter Adjustments & Application Considerations
Figure 4.29
2.
Press the
U
key to set the parameter to 10.00. The setting range is
0.01…99.99.
EXAMPLE
Operation Procedure: Configuring the Dead Band
Dead Band = 5
1.
Select Dead Band in the Adjustment function group.
Figure 4.30
2.
Press the
U
key to set the parameter to 5.0. The setting range is
–199.9…+999.9.
Figure 4.31
Using the Event Input
Feature — 900-TC8 &
900-TC16
Overview
When the appropriate option unit (refer to Tables 1.C and 1.E) is installed,
discrete (ON/OFF) inputs can be wired to the Bulletin 900 to cause the
controller to perform several pre-defined/configurable tasks. These inputs are
generically called event inputs.
c-sc
1.00
Cooling
coefficient
c-sc
10.00
C
c-db
0.0
Dead band
C
c-db
5.0