4-20
Parameter Adjustments & Application Considerations
The following table shows the relationship between the Multi-SP Uses
parameter value and the selected set point.
Note:
The set point can also be switched using PC communications. This is
supported by 900-TC8, 900-TC16, and 900-TC32.
Multi-SP Setup
EXAMPLE
Operation Procedure: To Select Set Points (0/1/2/3)
The following example configures the Number of Multi-SP Uses parameter to
2 (Multi-SP, 4 points). Refer to Table 4.I.
Before you configure the Number of Multi-SP Uses parameter, you must first
cancel protection from the Advanced Setting function group. For additional
details on how to cancel key protection, refer to page 4-33,
Using the Key Protect
Function Group
.
1.
Press the
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.33
Table 4.I
Multi-SP Uses Parameter Value
Selected Set Point
0
Select Set Point 0 value
1
Select Set Point 1 value
2
Select Set Point 2 value
3
Select Set Point 3 value
C
25
100
PV/SP
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...