Parameter Adjustments & Application Considerations
Parameters
Configuring the SP Upper-
and Lower-Limit Values
Set Point Limiter
The maximum allowable configuration range of the set point is limited by the
set point limiter parameter. The set point limiter is used to prevent someone
from configuring the set point to some value outside the maximum range
called for by the application, thereby preventing the control target from
reaching an abnormal temperature. The upper- and lower-limit values of the
set point limiter are configured from the Set Point Upper-Limit and Set Point
Lower-Limit parameters in the Initial Setting function group, respectively.
Figure 4.40
Table 4.S
Symbol
Parameter: Level
Description
eV-1
Event Input Assignment 1: Initial
Setting function group
Function of event input function
eV-2
Event Input Assignment 2: Initial
Setting function group
eV-m
Number of Multi-SP Uses: Initial
Setting function group
B
(setting possible)
Setting range
Changed to upper
limit value
Input type changed
Sensor range
Set point limitter
Changed to the
new upper limit
value
Set point
B
A
C
Set point
Set point
Sensor upper- and lower-limit values
Set point
Upper- and lower-limit values of the limitter
x
(setting not possible)
x
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...