Publication 900-UM007D-EN-E - January 2011
4-42
Parameter Adjustments & Application Considerations
Setting
Configuring the PV Color Change to Indicate Stable Status
To display the PV as a constant green color (to indicated a stable condition)
display when the PV is within
±
15.0
°
C of the set point, configure the PV
Color Change and PV Stable Band parameters.
PV Color Change =
r-gr
(Red to Green to Red)
PV Stable Band = 15.0
°
C
EXAMPLE
Operating Procedure
Note:
Make sure you release the protection to Move to the Advanced Setting
function group before you configure the PV Color Change and PV
Stable Band parameters since both parameters are located in the
Advanced Setting function group. (Refer to steps 1…8 on page 4-31.)
Figure 4.74
1.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.75
2.
Select the Move to Advanced Setting function group parameter by
pressing the
M
key.
Figure 4.76
C
25
100
PV/SP
in-t
5
Input type
amov
-169
Move to advanced function setting level
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...