Parameter Adjustments & Application Considerations
4-43
3.
Use the
D
key to enter
−
169
(the password).
Move to the Advanced Setting function group by pressing the
M
key or
leaving the setting for at least 2 seconds.
Figure 4.77
4.
Select the PV Color Change parameter by pressing the
M
key.
Figure 4.78
5.
Press the
U
key to set the parameter to
r-gr
.
Figure 4.79
6.
Select the PV Stable Band parameter by pressing the
M
key.
Figure 4.80
7.
Use the
U
key to set the parameter to 15.0.
Figure 4.81
8.
To return to the Initial Setting function group, press the
O
key for at
least 1 second.
9.
To return to the Operation function group, press the
O
key for at least
1 second.
Figure 4.82
init
off
Parameter
initialization
colr
red
PV change
color
colr
r-g.r
C
pv-b
5.0
PV stable band
C
pv-b
15.0
C
25
100
PV/SP