Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations
4-45
Parameters Related to Alarm Delays
Note:
The default time values are 0 (i.e., the ON and OFF delays are disabled).
Note:
The parameters are displayed when alarm functions are assigned and
when the alarm type is configured to any type but 0 (none).
EXAMPLE
Operating Procedure
The following example procedure shows how to configure ON and OFF delay
for Alarm Output 1.
An ON delay of 5 seconds and an OFF delay of 10 seconds will be configured.
Figure 4.84
1.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.85
2.
Select the Move to Advanced Setting function group parameter by
pressing the
M
key.
Figure 4.86
Table 4.AA
Parameter Name
Symbol
Configurable Range
Alarm 1 ON delay
a1on
0…999 (s)
Alarm 2 ON delay (900-TC8, 900-TC16)
a2on
0…999 (s)
Alarm 3 ON delay (900-TC8)
a3on
0…999 (s)
Alarm 1 OFF delay
a1of
0…999 (s)
Alarm 2 OFF delay (900-TC8, 900-TC16)
a2of
0…999 (s)
Alarm 3 OFF delay (900-TC8)
a3of
0…999 (s)
C
25
100
PV/SP
in-t
5
Input type
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...