Publication 900-UM007D-EN-E - January 2011
Parameter Adjustments & Application Considerations
4-51
EXAMPLE
Operating Procedure: Loop Break Alarm Configurations
In this example, the LBA Detection Time is configured to 10, the LBA Level is
configured to 8.0, and the LBA Band is configured to 3.0.
Figure 4.96
1.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.97
2.
Select the Alarm 1 Type parameter by pressing the
M
key.
Figure 4.98
3.
Press the
U
key to configure the Alarm 1 Type parameter value to 12.
Figure 4.99
4.
Select the Move to Advanced Setting function group parameter by
pressing the
M
key.
Figure 4.100
C
25
100
PV/SP
in-t
5
Input type
alt1
2
Alarm 1 type
alt1
12
amov
0
Move to Advanced
Setting Function Group