Publication 900-UM007D-EN-E - January 2011
4-64
Parameter Adjustments & Application Considerations
EXAMPLE
Operating Procedure
The following procedure configures the Transfer Output Type as a SP with a
range (limit) of
−
50…200.
Figure 4.137 — Operation function group
1.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 4.138
2.
Select the Transfer Output Type parameter by pressing the
Key
.
Figure 4.139
3.
Press the
U
key to select
sp
(set point).
Figure 4.140
4.
Select the Transfer Output Upper-Limit parameter by pressing the
M
key.
Figure 4.141
C
25
100
PV/SP
in-t
5
Input type
tr-t
off
Transfer output
type
tr-t
s
p
C
tr-h
1300
Transfer output
upper limit