Parameter Adjustments & Application Considerations
Controller. The ON/OFF count alarm configured value function is disabled
by setting the ON/OFF count alarm configured value to 0.
ON/OFF Counter Reset Function
The ON/OFF counter can be reset for a specific control output.
Note:
After the counter has been reset, the control output ON/OFF count
monitor value will be automatically returned to 0.
If an error occurs in the control output ON/OFF counter data, the
ON/OFF count monitor value will be configured to 9999 and an
ON/OFF count alarm will occur. The alarm can be cleared by resetting
the ON/OFF counter.
Operating Procedure
This procedure sets the Control Output 1 ON/OFF Alarm Setting parameter
to 10 (1,000 times).
1.
Press the
O
Key for at least three seconds to move from the Operation
to the Initial Setting function group.
Figure 4.201
Table 4.AO
Parameter Name
Configurable
Range
Unit
Default
Control Output 1 ON/OFF Alarm Setting
0 to 9999
100 times
0
Control Output 2 ON/OFF Alarm Setting
(900-TC8 & 900-TC16)
0 to 9999
100 times
0
Table 4.AP
Parameter Name Configurable Range
Unit
Default
ON/OFF Counter
Reset
0: Disable the counter reset function.
1: Reset the control output 1 ON/OFF
counter.
2: Reset the control output 2 ON/OFF
counter (900-TC8 & 900-TC16).
---
0
in-t
5
Input Type
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...