Publication 900-UM007D-EN-E - January 2011
5-40
Parameter Functions & Definitions
Wait Band
Conditions of Use:
The Program Pattern parameter must NOT be set to
OFF.
Function:
This parameter enables you to configure the stable band within
which the soak time is measured for the simple program function.
➊
Set NONE as the unit for Controllers with 0…50 Millivolt Inputs.
Related Parameters
•
Program Start, Soak Time Remain (Operation function group, page
5-15)
•
Soak Time (Adjustment function group, page 5-39)
•
Program Pattern (Initial Setting function group, page 5-57)
•
Soak Time Unit (Advanced Setting function group, page 5-96)
MV at Stop
Conditions of Use:
The control method must be configured for 2-PID
control. The MV at Stop and Error Addition parameter must be configured to
ON.
Function:
This parameter allows you to configure the amount the MV
(process output) is OPEN/ON when the RUN/STOP status changes from
RUN to STOP.
Table 5.AS
Controller Type
Configurable
Range
Units
Default
With Thermocouple or Resistance
Thermometer (RTD)
OFF or
0.1…999.9
°
C or
°
F
➊
Off
With Analog Inputs
OFF or
0.01…99.99
%FS
Table 5.AT
Configurable Range
Units
Default
−
5.0…105.0 for standard control
−
105.0…105.0 (heating/cooling control)
%
0.0
wt-b
mv-s
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...