Publication 900-UM007D-EN-E - January 2011
5-44
Parameter Functions & Definitions
Related Parameters
•
Proportional Bband (Adjustment function group, page 5-35)
Extraction of Square Root Low-cut Point,
Condition of Use:
The input type must be an analog input, and the
Extraction of Square Root Enable parameter must be set to ON.
Function:
This parameter sets the extraction of square root low-cut point
used for the inputs. The low-cut point is used for extracting the square root for
flow rate sensors. The data after extracting the square root is shown below.
Related Parameters
•
Extraction of Square Root Enable (Initial Setting function group, page
5-44)
Table 5.AZ
Configurable Range
Units
Default
0.0...100
%
0.0
5qrp
Argument 1 (input data)
Operation result
100% FS
0
100% FS
Extraction of square
root low-cut point