Parameter Functions & Definitions
Set Point Upper-Limit,
Set Point Lower-Limit
Function:
These parameters allow you to configure the maximum allowable
range for an operator to enter the set point value. The SP can be configured
within the range defined by the Upper- and Lower-Limit values in the Set
Point Upper-Limit and Set Point Lower-Limit parameters. If an attempt is
made to enter a SP value outside the upper or Lower-Limit from the keypad
the set point display will flash at the configured maximum upper- or
Lower-Limit value.
If the temperature Input Type or temperature units are changed, the set point
Upper-Limit and set point Lower-Limit are forcibly changed by the controller
to the default Upper- and Lower-Limits of the newly configured sensor.
For a temperature input, the decimal point position is dependent on the
currently selected sensor. For an analog input, it is dependent on the Decimal
Point parameter setting.
Related Parameters
•
Input Type (page 5-50), Temperature Units (
°
C/
°
F) Selection (page
5-53) (Initial Setting function group)
Table 5.BJ — Controllers with Thermocouple/Resistance Thermometer Inputs
Parameter
Input Type
Configurable Range
Units
Default
Set Point
Upper-Limit
Temperature
SP Lower-Limit + 1 to Input
range Upper-Limit
EU
1300
Millivolt
SP Lower-Limit + 1 to scaling
Upper-Limit
EU
100
Set Point
Lower-Limit
Temperature
Input range Lower-Limit to SP
Upper-Limit
−
1
EU
−
200
Millivolt
Scaling Lower-Limit to SP
Upper-Limit
−
1
EU
0
Table 5.BK — Controllers with Analog Inputs (900-TC8 & 900-TC16)
Parameter
Configurable Range
Units
Default
Set Point Upper-Limit
SP Lower-Limit + 1 to scaling
Upper-Limit
EU
100
Set Point Lower-Limit
Scaling Lower-Limit to SP
Upper-Limit
−
1
EU
0
sl-h
sl-l
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...