Publication 900-UM007D-EN-E - January 2011
5-62
Parameter Functions & Definitions
Alarm 2 Hysteresis
Conditions of Use:
Alarm 2 must be assigned. The alarm 2 type must NOT
be 0, 12, or 13.
Alarm 3 Hysteresis
Conditions of Use:
Alarm 3 must be assigned. The alarm 3 type must NOT
be 0, 12, or 13.
Function:
These parameters set the hysteresis (allowed deviation from the
configured alarm value) for alarms 1, 2, and 3.
Note:
Set
None
as the unit for 0 to 50 millivolt.
Related Parameters
•
Alarm value 1 to 3 (page 5-16), Alarm value upper limit 1 to 3 (page
5-18), Alarm value lower limit 1 to 3 (page 5-18) (Operation function
group)
•
Alarm 1 to 3 type (Initial Setting function group, page 5-59)
Transfer Output Type (900-TC8, 900-TC16)
Conditions of Use:
An analog current output must be assigned/configured
Function:
This parameter allows you to configure the analog current output
for a specific type of transfer output. Refer to Table 5.BU.
Note:
If the analog current output is NOT used as a transfer output, configure
this parameter to OFF (default).
Table 5.BS
Controller Models
Configurable Range Units
Default
Model with thermocouple/resistance
thermometer universal input
0.1...999.9
°
C or
°
F 0.2
Model with analog input
0.01...99.99
%FS
0.02
alh2
alh3
tr-t
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...