Publication 900-UM007D-EN-E - January 2011
Parameter Functions & Definitions
5-65
Number of Multi-SP Uses (900-TC8, 900-TC16)
Conditions of Use:
An event input unit must be assigned. An optional event
input unit must be installed in the controller.
Function:
Multi-SP is a function for setting set points 0 to 3 in advance, and
switching between these set points using a combination of event input
ON/OFF signals. The number of Multi-SP Uses parameter is used to switch
between using two and four preset set points.
Whether the Event Input Assignments 1 and 2 parameters are displayed or
hidden is determined by the Number of Multi-SP Uses parameter setting.
The following tables show the relationships between ON/OFF combinations
of event inputs 1 and 2 and selected set points.:
Table 5.BX
Configurable Range
Default
0 to 2
1
Table 5.BY — Controllers with Event Inputs 1 and 2 (Two Event Inputs)
Event Input Assignment 1
Event Input Assignment 2
Number or
Multi-SP uses
0
Displayed (Multi-SP not used).
1
Hidden (Multi-SP, 2 points)
Displayed (Event input 2 not
used as multi-SP switch).
2
Hidden (Multi-SP, 4 points).
Table 5.BZ —Number of Multi-SP Uses: 1
Event input 1
Selected set point
OFF
Set point 0
ON
Set point 1
Table 5.CA — Number of Multi-SP Uses: 2
Event input 1
Event input 2
Selected set point
OFF
OFF
Set point 0
ON
OFF
Set point 1
OFF
ON
Set point 2
ON
ON
Set point 3
ev-m
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...