Parameter Functions & Definitions
5-67
Function:
The following functions can be assigned to event inputs 1 and 2:
• RUN/STOP
• Auto/Manual Switch
• Program Start
• Invert Direct/Reverse Operation
• 100% AT Execute/Cancel
• 40% AT Execute/Cancel
• Setting Change Enable/Disable
• Alarm Latch Cancel
Default:
• Event Input Assignment 1:
none
• Event Input Assignment 2:
stop
.
Note: 1
PRST (Program Start) can be configured even when the Program Pat-
tern parameter is configured to OFF, but the function will be dis-
abled.
Note: 2
This function can be configured for heating/cooling control, but the
function will be disabled.
Related Parameters
•
SP0 to SP3 (Adjustment function group, page 5-33)
•
Number of multi-SP uses (Initial Setting function group, page 5-65)
Table 5.CC
Selection
Function
none
None
stop
RUN/STOP
manu
Auto/Manual
prst
Program start (see note 1.)
drs
Invert Direct/Reverse Operation
at-2
100% AT Execute/Cancel
at-1
40% AT Execute/ Cancel (see note 2)
wtpt
Setting Change Enable/Disable
lat
Alarm Latch Cancel
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...