Publication 900-UM007D-EN-E - January 2011
5-92
Parameter Functions & Definitions
Related Parameters
•
Process Value/Set Point (Operation function group, page 5-8)
•
Alarm 1 Type (Initial Setting function group, page 5-59)
•
LBA Detection Time, LBA Level (Advanced Setting function group,
page 5-90)
Control Output 1 Assignment
Conditions of Use:
The Transfer Output Type parameter must be set to OFF
when the Control Output is an analog current output.
Function:
This parameter allows you to configure the output function
assigned to Control Output 1.
Related Parameters
•
Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
Transfer Output Type (page 5-62) (Initial Setting function group)
Table 5.DK
Control Output 1 Function
Default
None
:
No control output function is assigned
o
o
:
Heating control output is output
c-o
:
Cooling control output is output
➊
alm1
:
Alarm 1 is output
➋
alm2
:
Alarm 2 is output
➋
alm3
:
Alarm 3 is output
➋
p.end
:
Program end is output
➋➌
ralm
:
Control output ON/OFF count alarm
➋
➊
If
c-o
(cooling Control Output) is assigned for standard control, a value equivalent to 0% is output.
➋
Can be selected for relay and voltage outputs only
➌
Can be selected only when the program pattern is not set to OFF, but the function is disabled.
out1
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...