Publication 900-UM007D-EN-E - January 2011
5-96
Parameter Functions & Definitions
Related Parameters
•
Standard or Heating/Cooling (page 5-55), Program Pattern (page 5-57),
(Initial Setting function group)
Character Select LED
Function:
This parameter allows you to select the LED display type for your
controller. The following two types of displays are available:
•
11-segment display
•
7-segment display
When set to
on
, an 11-segment display is used.
Soak Time Units
Conditions of Use:
The Program Pattern parameter must NOT be set to
OFF.
Table 5.DO
Auxiliary Output 3 Function
Default
none
:
No function is assigned to auxiliary output 3
alm3
➌
o
:
Heating Control Output is output
c-o
:
Cooling Control Output is output
➊
alm1
:
Alarm 1is output
alm2
:
Alarm 2 is output
alm3
:
Alarm 3 is output
p.end
:
Program end is output
➋
ralm
:
Control output ON/OFF count alarm
➋
➊
If
c-o
is assigned for standard control, a value equivalent to 0% will be output.
➋
Can be selected only when the program pattern is not set to OFF, but the function is disabled.
➌
If the Standard or Heating/Cooling parameter is set to heating/cooling control when there is no Control Output
2 (900-TC8), control automatically switches to
c-o
.
Table 5.DP
Selections
Default
on
: 11-segment display,
off
: 7-segment display
on
csel
t-u
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...