Publication 900-UM007D-EN-E - January 2011
5-102
Parameter Functions & Definitions
Monitor/ Setting Item
* (*:
1 to 5)
Conditions of Use:
The PF Setting parameter must be configured to PFDP.
Function:
When you configure the PF Key parameter to Monitor/Setting
Item it enables using the function key to display monitor/setting items. The
items that will be displayed are configured using the Monitor/Setting Item 1 to
5 parameters. The settings are listed in the following table.
Note:
The MV for heating and cooling control is set in the MV Display
Selection parameter.
Related Parameter
•
PF Setting (page 5-101), MV Display Selection (page 5-103) (Advanced
Setting function group)
Table 5.DY
Set Value Parameter
Remarks
Monitor/Setting Symbol
0
Disabled
---
1
PV/SP/Multi-SP
Can be set. (SP)
---
2
PV/SP/MV
Can be set. (SP)
---
3
PV/SP/Soak time remain
Can be set. (SP)
---
4
Proportional band (P)
Can be set.
p
5
Integral time (I)
Can be set.
c
6
Derivative time (D)
Can be set.
d
7
Alarm value 1
Can be set.
al-1
8
Alarm value upper limit 1
Can be set.
al 1h
9
Alarm value lower limit 1
Can be set.
al il
10
Alarm value 2
Can be set.
al-2
11
Alarm value upper limit 2
Can be set.
al2h
12
Alarm value upper limit 2
Can be set.
al2l
13
Alarm value lower limit 2
Can be set.
al-3
14
Alarm value 3
Can be set.
al3h
15
Alarm value upper limit 3
Can be set.
al3l
pfd
*
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...