Publication 900-UM007D-EN-E - January 2011
6-2
Troubleshooting & Error Indication
Operation at Error
•
After an error occurs, the error is displayed and the alarm output
functions as if the Upper-Limit has been exceeded.
•
If you configure the Input Error Output parameter in the Advanced
Setting function group to ON, the Alarm 1 output turns ON whenever
an input error occurs.
•
An error message is displayed when the PV, PV/SP, or PV/MV is
displayed.
•
The control output turns OFF when the manual MV, MV at stop, or
MV at PV error is configured, the control output corresponds to the
configured value.
Display Range Exceeded
Meaning
This is not an error, but rather, it is displayed if the process value (sensor
input) exceeds the display range when the control range is larger than the
display range.
The display ranges are shown below (with decimal points omitted).
•
When less than
−
1,999
[[[[
•
When more than 9,999
]]]]
Action
Control continues, allowing normal operation. The message is displayed when
the PV, PV/SP, or PV/MV is displayed.
[[[[
]]]]
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...