A-1
Publication 900-UM007D-EN-E - January 2011
Appendix
A
Specifications
For the setting ranges for each sensor input, refer to page A-9.
Available from Little Fuse or Bussmann (part no. GDC-2A).
For the setting ranges for each sensor input, refer to page A-9.
Always connect an AC load to a Triac output. The output will not turn OFF if a DC load is connected.
Table A.A
Technical/Control
Supply Voltage
100…240V AC, 50/60 Hz
24V AC, 50/60 Hz/24V DC
Operating Voltage Range
85 to 110% of rated supply voltage
Power Consumption
900-TC16
7.5 VA
5 VA/3 W
900-TC8
10 VA
5.5 VA/4 W
900-TC32
5.5 VA
3 VA/2W
Recommended line fuse
Type: T2A, 250V AC, time lag, low shut-off capacity
Sensor Input
Sensor Input
Temperature Input Type
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PL II
Platinum resistance thermometer: Pt100, JPt100
Infrared temperature sensor: 10…70
°
C, 60…120
°
C, 115…165
°
C, 140…260
°
C
Millivolt input: 0 to 50 mV
Supported by 900-TC8 & 900-TC16:
Controllers with Analog Inputs
Current input: 4…20 mA, 0…20 mA (Input impedance: 150
Ω
max.)
Voltage input: 1…5V, 0…5V, 0…10V (Input impedance: 1 M
Ω
max.)
Control Output
Relay Output 900-TC16
Relay output:
SPST-NO, 250V AC, 3 A (resistive load), electrical durability: 100,000
operations
Min. applicable load: 5V, 10 mA
Triac (AC) output
SPST-NO, 250V AC, 3 A (resistive load), electrical durability: 1,000,000
operations
Load power supply voltage: 75…250V AC
Leakage current: 5 mA max. (250V AC, 60 Hz)
900-TC8
Relay output:
SPST-NO, 250V AC, 5 A (resistive load), electrical durability: 100,000
operations
Min. applicable load: 5V, 10 mA
Triac (AC) output:
SPST-NO, 250V AC, 3 A (resistive load), electrical durability: 1,000,000
operations
Load power supply voltage: 75…250V AC
Leakage current: 5 mA max. (250V AC, 60 Hz)
900-TC32
Relay output:
SPST-NO, 250V AC, 2 A (resistive load), electrical durability: 100,000
operations
Min. applicable load: 5V, 10 mA
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...