Table A.F — List of Global Temperature (GT) Input Types
Input Type
Specifications
Set
Value
Input Setting Range
Input Indication Range
Cont
rol
ler T
ype w
it
h
T
hermoco
upl
e and
Re
sistan
ce T
hermom
eter Mult
i-i
npu
ts
Resistance
Thermometer
Pt100
0
−
200…850 (
°
C)/
−
300…1,500 (
°
F)
-220…870 (
°
C)/-340…1540 (
°
F)
1
−
199.9…500.0 (
°
C)/
−
199.9…900.0 (
°
F)
-199.9…520 (
°
C)/-199.9…940 (
°
F)
2
0.0…100.0 (
°
C)/0.0…210.0 (
°
F)
-20.0…120 (
°
C)/-40…250 (
°
F)
JPt100
3
−
199.9…500.0 (
°
C)/
−
199.9…900.0 (
°
F)
-199.9…520 (
°
C)/-199.9…940 (
°
F)
4
0.0…100.0 (
°
C)/0.0…210.0 (
°
F)
-20.0…120 (
°
C)/-40…250 (
°
F)
Thermocouple
K
5
−
200…1,300 (
°
C)/
−
300…2,300 (
°
F)
-220…1320 (
°
C)/-340…2340 (
°
F)
6
−
20.0…500.0 (
°
C)/0.0…900.0 (
°
F)
-40…520 (
°
C)/-40…940 (
°
F)
J
7
−
100…850 (
°
C)/
−
100…1,500 (
°
F)
-120…870 (
°
C)/-140…1540 (
°
F)
8
−
20.0…400.0 (
°
C)/0.0…750.0 (
°
F)
-40…420 (
°
C)/-40…790 (
°
F)
T
9
−
200…400 (
°
C)/
−
300…700 (
°
F)
-220…420 (
°
C)/-340…740 (
°
F)
10
−
199.9…400.0 (
°
C)/
−
199.9…700.0 (
°
F)
-199.9…420 (
°
C)/-199.9…740 (
°
F)
E
11
0…600 (
°
C)/0…1,100 (
°
F)
-220…620 (
°
C)/-340…1140 (
°
F)
L
12
−
100…850 (
°
C)/
−
100…1,500 (
°
F)
-120…870 (
°
C)/-140…1540 (
°
F)
U
13
−
200…400 (
°
C)/
−
300…700 (
°
F)
-220…420 (
°
C)/-340…740 (
°
F)
14
−
199.9…400.0 (
°
C)/
−
199.9…700.0 (
°
F)
-199.9...420 (
°
C)/-199.9…740 (
°
F)
N
15
−
200…1,300 (
°
C)/
−
300…2,300 (
°
F)
-220…1320 (
°
C)/-340…2340 (
°
F)
R
16
0…1,700 (
°
C)/0…3,000 (
°
F)
-20…1720 (
°
C)/-40…3040 (
°
F)
S
17
0…1,700 (
°
C)/0…3,000 (
°
F)
-20…1720 (
°
C)/-40…3040 (
°
F)
B
18
100…1,800 (
°
C)/300…3,200 (
°
F)
0…1820 (
°
C)/0…3240 (
°
F)
Infrared
(non-contact)
temperature
sensor
10…70
°
C
19
0…90 (
°
C)/0…190 (
°
F)
-20…130 (
°
C)/-40…270 (
°
F)
60…120
°
C
20
0…120 (
°
C)/0…240 (
°
F)
-20…160 (
°
C)/-40…320 (
°
F)
115…165
°
C
21
0…165 (
°
C)/0…320 (
°
F)
-20…205 (
°
C)/-40…400 (
°
F)
140…260
°
C
22
0…260 (
°
C)/0…500 (
°
F)
-20…300 (
°
C)/-40…580 (
°
F)
Millivolt input
0…50 mV
23
Either of the following ranges, by scaling:
−
1,999…9,999
−
199.9…999.9
5%... 105% of setting range. The
display shows - 1999 to 9999
(numeric range with decimal point
omitted).
Thermocouple
W
24
0…2300 (
°
C)/0…3200 (
°
F)
-20…2320 (
°
C)/-40…3240 (
°
F)
PL-II
25
0…1300 (
°
C)/0…2300 (
°
F)
-20…1320 (
°
C)/-40…2340 (
°
F)
Cont
rol
lers wi
th
Analo
g In
put
s
Current Input
4...20 mA
0
Any of the following ranges, by scaling:
-1,999...9,999
-199.9...999.9
-19.99...99.99
-1.999...9.999
-5%...105% of setting range. The
display shows -1999...9999 (numeric
range with decimal point omitted).
0...20 mA
1
Voltage Input
1...5 V
2
0...5 V
3
0...10 V
4
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...