Calibrating an Analog Voltage (e.g., 1…5V DC) Input (900-TC8 &
900-TC16)
In this example, calibration is shown for a Controller with an Analog Voltage
Input (Input Type 2, 3, or 4).
1.
Connect the power supply.
2.
Connect an STV and DMM to the voltage input terminals, as shown in
the following diagram.
Figure C.31
3.
Turn the power ON.
Figure C.32
4.
Move to the calibration function group.
This starts the 30-minute aging timer. This timer provides an
approximate timer for aging. After 30 minutes have elapsed, the No. 2
display changes to 0. You can advance to the next step in this procedure
even if 0 is not displayed.
5.
When the
M
key is pressed, the status changes as shown in the figure
below.
The No. 2 display at this time shows the currently entered count value in
hexadecimal. Set the STV as follows:
•
Input Type 2 or 3: 5V
•
Input Type 4: 10V
Allow the count value on the No. 2 display to fully stabilize, then press
the
D
key to temporarily register the calibration settings.
If this count value is outside of the specified range, the No. 2 display will
flash and the count value will not be temporarily registered.
STV
DMM
−
+
9
10
4
5
Input Power Supply
900-TC16
STV
DMM
−
+
1
2
19
20
Input Power Supply
900-TC8
adj
30
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...