Publication 900-UM007D-EN-E - January 2011
Configuration & Basic Operation
3-19
Figure 3.22
2.
The Input Type is displayed. When you are monitoring/configuring the
Input Type for the first time, the set value is
0
: K type thermocouple
default. (
0
is set if you have a platinum resistance thermometer
compatible controller. To select a different sensor, press the
U
or
D
keys. This changes the Set Value (refer to Table 3.A) to match your
desired sensor input.
Figure 3.23
3.
Select the Temperature Unit parameter by pressing the
M
key.
Note:
The default is
c
:
°
C. To configure
f
:
°
F, press the
U
key.
Figure 3.24
4.
Select the Control Period (OUT1) parameter by pressing the
M
key.
Note:
The default is 20.
Figure 3.25
5.
Select the Direct/Reverse Operation parameter by pressing the
M
key.
Note:
The default is
or-r
: reverse operation. To configure
or-d
:
direct operation, press the
U
key.
Figure 3.26
C
3
0
0
in
-
t
5
Input type
d
-
u
c
Temperature unit
cp
20
Control period
(heat)
orev
or
-
r
Direct/reverse
operation
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...