Publication 900-UM007D-EN-E - January 2011
3-22
Configuration & Basic Operation
Control Output (Cooling); Auxiliary Output 1: Alarm 1; Auxiliary Output 2:
Alarm 2
1.
Press the
O
key for at least 3 seconds to move from the Operation
function group to the Initial Setting function group.
Figure 3.29
2.
Select the Standard or Heating/Cooling Control Mode parameter by
pressing the
M
key.
Figure 3.30
Figure 3.31
3.
Press the
U
key to set the parameter to
h-c
(Heating/Cooling)
Control Mode.
Note:
The following output assignments do not need to be set because
they are set automatically as defaults by changing the control mode, but
they are shown here as a reference for checking the assignments for each
output.
Figure 3.32
4.
Select the Move to Advanced Setting function group parameter by
pressing the
M
key.
5.
Press the
D
key to enter the password (
−
169
), and move from the
Initial Setting function group to the Advanced Setting function group.
Figure 3.33
C
2
5
100
PV/SP
in
-
t
5
Input type
5-h
c
stnd
Standard or
heating/cooling
5-h
c
h-
c
amov
0
Move to Advanced
Setting Function Group
Summary of Contents for Allen-Bradley 900-TC16
Page 1: ...USER MANUAL Bulletin 900 TC8 900 TC16 900 TC32 Series B Temperature Controllers...
Page 2: ...2...
Page 72: ...Publication 900 UM007D EN E January 2011 3 2 Configuration Basic Operation Figure 3 3 900 TC32...
Page 136: ...Publication 900 UM007D EN E January 2011 3 66 Configuration Basic Operation Notes...
Page 340: ...Publication 900 UM007D EN E January 2011 5 112 Parameter Functions Definitions Notes...
Page 350: ...Publication 900 UM007D EN E January 2011 6 10 Troubleshooting Error Indication Notes...
Page 406: ...Publication 900 UM007D EN E January 2011 D 8 Glossary Notes...