Protective Trip and Warning Functions
Table 278 - Under kVA Trip Delay (Parameter 403)
Under kVA Trip Level
Under kVA Trip Level (Parameter 404) allows you to define the apparent power
(kVA) at which the E300 Electronic Overload Relay trips on an under apparent
power (kVA). It is user-adjustable from 0…2,000,000 kVA.
Table 279 - Under kVA Trip Level (Parameter 404)
Under kVA Warning
The E300 Electronic Overload Relay indicates an Under kVA warning if:
•
No warning currently exists
•
Under kVA Warning is enabled
•
Current is present
•
Voltage is present
•
Under kVA Inhibit Time has expired
•
The total apparent power (kVA) is equal to or less than the Under kVA
Warning Level
When the Under kVA Warning conditions are satisfied, the:
•
TRIP/WARN LED flashes a yellow 2-long / 7-short blink pattern
•
Bit 6 in Power Warning Status (Parameter 12) sets to 1
Default Value
1.0
Minimum Value
0.1
Maximum Value
25.0
Parameter Type
USINT
Size (Bytes)
1
Scaling Factor
10
Units
Seconds
Default Value
0.000
Minimum Value
0.000
Maximum Value
2,000,000.000
Parameter Type
DINT
Size (Bytes)
4
Scaling Factor
1000
Units
kVA
IMPORTANT
The Under kVA Inhibit Time starts after a phase voltage transitions from 0V to
20V L-L and a phase of load current transitions from 0 A to 30% of the
minimum FLA setting of the device. The E300 Electronic Overload Relay does
not begin monitoring for an under apparent power (kVA) condition until the
Under kVA Inhibit Time expires.
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......