Chapter 8
Metering and Diagnostics
Time to Trip
When the measured motor current exceeds the trip rating of the E300 Electronic
Overload Relay, Overload Time to Trip (Parameter 2) indicates the estimated
time remaining before an overload trip occurs. When the measured current is
below the trip rating, the Overload Time to Trip value is reported as 9,999
seconds.
Table 356 - Overload Time to Trip (Parameter 2)
Time To Reset
After an overload trip, the E300 Electronic Overload Relay reports the time
remaining until the device can be reset through Overload Time to Reset
(Parameter 3). When the % Thermal Capacity Utilized value falls to or below the
Overload Reset Level (Parameter 174), the Overload Time to Reset value
indicates zero until the overload trip is reset. After an overload trip is reset, the
Overload Time to Reset value is reported as 0 seconds.
Table 357 - Overload Time to Reset (Parameter 3)
Default Value
9999
Minimum Value
0
Maximum Value
9999
Parameter Type
UINT
Size (Bytes)
2
Scaling Factor
1
Units
Seconds
Default Value
0
Minimum Value
0
Maximum Value
9999
Parameter Type
UINT
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......