352
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 8
Metering and Diagnostics
Table 463 - Analog Module 1 Status (Parameter 123)
Analog Module 2
Analog Module 2 – Input Channel 00
Analog Module 2 – Input Channel 00 (Parameter 114) reports the monitored
value of Analog Module 2 – Input Channel 00.
Table 464 - Analog Module 2 – Input Channel 00 (Parameter 114)
Analog Module 2 – Input Channel 01
Analog Module 2 – Input Channel 01 (Parameter 115) reports the monitored
value of Analog Module 2 – Input Channel 01.
Bit
Function
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
X
Input Channel 00 Open Circuit
X
Input Channel 00 Over Range
X
Input Channel 00 Under Range
X
Input Channel 01 Open Circuit
X
Input Channel 01 Over Range
X
Input Channel 01 Under Range
X
Input Channel 02 Open Circuit
X
Input Channel 02 Over Range
X
Input Channel 02 Under Range
X
Output Channel 00 Open Circuit
X
Output Channel 00 Hold Last State
Mode Active
X
Output Channel 00 Over Range
X
Output Channel 00 Under Range
X
Analog Module Configured
X
Analog Module Warning (Module
Number Dial Changed)
X
Analog Module Faulted
Default Value
0
Minimum Value
-32768
Maximum Value
32767
Parameter Type
INT
Size (Bytes)
2
Scaling Factor
1
Units
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......