Rockwell Automation Publication 193-UM015D-EN-P - February 2015
385
EtherNet/IP Communications
Chapter 9
Download the EDS File
Embedded in the Module
The EDS file for the E300 Electronic Overload Relay EtherNet/IP
Communication Module is embedded within the module. Using RSLinx Classic,
you can install the E300 Electronic Overload Relay EtherNet/IP
Communication Module's EDS file from the RSLinx Classic RSWho screen
using these steps:
1.
Open RSLinx Classic and browse the EtherNet/IP network that has the
E300 Electronic Overload Relay. It will be identified with a yellow
question mark. Right click on the unrecognized device and select "Upload
EDS File from Device".
2.
Using the EDS Wizard, install the embedded E300 Electronic Overload
Relay EtherNet/IP Communication Module EDS file.