424
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Chapter 9
EtherNet/IP Communications
Module Status
None
—
The E300 EtherNet/IP Communication Module is not
receiving power.
Check the control power connection on the A1 and A2
terminals of the E300 EtherNet/IP Control Module.
Green, Red, Not
Illuminated
Flashing (once)
Normal
This is a normal power-up sequence.
Green
Flashing
The E300 EtherNet/IP Communication Module is not
being scanned by the EtherNet/IP master.
Check the Ethernet scan list for the correct scanner
configuration.
Green
Solid
Normal operating state, the E300 EtherNet/IP
Communication Module is allocated to its master.
No action is required.
Red
Flashing
One or more EtherNet/IP connections timed out.
Reset the E300 EtherNet/IP Communication Module.
The E300 Overload Relay is in a fault state.
Reset the E300 EtherNet/IP Communication Module or
verify the validity of the data in the configuration
assembly.
Red
Solid
Diagnostics test failed on power-up/reset.
Cycle power to the device. If the fault still exists, replace
the device.
Link1 or Link2
None
—
The E300 EtherNet/IP Communication Module is not
properly connected to an Ethernet network.
Check the Ethernet cabling to make sure it is properly
installed.
Green
Flashing
The Ethernet network is properly connected.
No action is required.
Green
Solid
Communications are occurring on the Ethernet network. No action is required.
Status LED
Color
State
Possible Cause
Corrective Action
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......