474
Rockwell Automation Publication 193-UM015D-EN-P - November 2013
Appendix B
Parameter List
Device Setup
(continued)
192
WarningEnableC
C.Protection.PTCWarningEn
C.Protection.ModuleMismatchWarningEn
C.Protection.ExpansionBusWarningEn
C.Protection.NumberOfStartsWarningEn
C.Protection.OperatingHoursWarningEn
Bitmask used to
enable/disable
control-based
warnings
UINT
2
1
Bit0= Reserved
Bit1= PTCWarning
Bit2= DLXWarning
Bit3= Reserved
Bit4= Reserved
Bit5= Reserved
Bit6= Reserved
Bit7= ConfigWarning
Bit8= OptionMatchWarn
Bit9= DLXFBTimeoutWarn
Bit10= ExpansionBusWarn
Bit11= PMNumberOfStarts
Bit12= PMOperatingHour
0
193
WarningEnableA
C.Protection.Analog1Ch00WarningEn
C.Protection.Analog1Ch01WarningEn
C.Protection.Analog1Ch02WarningEn
C.Protection.Analog2Ch00WarningEn
C.Protection.Analog2Ch01WarningEn
C.Protection.Analog2Ch02WarningEn
C.Protection.Analog3Ch00WarningEn
C.Protection.Analog3Ch01WarningEn
C.Protection.Analog3Ch02WarningEn
C.Protection.Analog4Ch00WarningEn
C.Protection.Analog4Ch01WarningEn
C.Protection.Analog4Ch02WarningEn
Bitmask used to
enable/disable
analog-based
warnings
UINT
2
1
Bit0= InAnMod1Ch00Warn
Bit1= InAnMod1Ch01Warn
Bit2= InAnMod1Ch02Warn
Bit3= InAnMod2Ch00Warn
Bit4= InAnMod2Ch01Warn
Bit5= InAnMod2Ch02Warn
Bit6= InAnMod3Ch00Warn
Bit7= InAnMod3Ch01Warn
Bit8= InAnMod3Ch02Warn
Bit9= InAnMod4Ch00Warn
Bit10= InAnMod4Ch01Warn
Bit11= InAnMod4Ch02Warn
0
194
Reserved
195
SetOperatingMode
Logic personality
Selection
USINT
1
1
2
54
2
196
InPt00Assignment
C.Pt00InputFunction_0
C.Pt00InputFunction_1
C.Pt00InputFunction_2
C.Pt00InputFunction_3
Assignment for
Input Point 00
function
USINT
1
1
0=Normal
1=TripReset
2=RemoteTrip
3=ActivateFLA2
4=ForceSnapshot
5=EmergencyStart
6=TestMode
7=L1LossArm
8=L2LossArm
9=L3LossArm
10=L1L2LossArm
11=L2L3LossArm
12=L1L3LossArm
13=L1L2L3LossArm
0
197
InPt01Assignment
C.Pt01InputFunction_0
C.Pt01InputFunction_1
C.Pt01InputFunction_2
C.Pt01InputFunction_3
Assignment for
Input Point 01
function
USINT
1
1
0=Normal
1=TripReset
2=RemoteTrip
3=ActivateFLA2
4=ForceSnapshot
5=EmergencyStart
6=TestMode
7=L1LossArm
8=L2LossArm
9=L3LossArm
10=L1L2LossArm
11=L2L3LossArm
12=L1L3LossArm
13=L1L2L3LossArm
0
198
InPt02Assignment
C.Pt02InputFunction_0
C.Pt02InputFunction_1
C.Pt02InputFunction_2
C.Pt02InputFunction_3
Assignment for
Input Point 02
function
USINT
1
1
0=Normal
1=TripReset
2=RemoteTrip
3=ActivateFLA2
4=ForceSnapshot
5=EmergencyStart
6=TestMode
7=L1LossArm
8=L2LossArm
9=L3LossArm
10=L1L2LossArm
11=L2L3LossArm
12=L1L3LossArm
13=L1L2L3LossArm
0
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......