Rockwell Automation Publication 193-UM015D-EN-P - February 2015
537
EtherNet/IP Information
Appendix C
The following services are implemented for the Wall Clock Time Object.
Table 581 - Wall Clock Time Object Common Services
DPI Fault Object — CLASS CODE 0x0097
This object provides access to fault information within the device.
The following class attributes are supported:
5
Set / SSV
Date and Time
(Local Time)
DINT[7] –
Array of seven DINTs
Current adjusted time in human readable format.
DINT[0] – year
DINT[1] – month
DINT[2] – day
DINT[3] – hour
DINT[4] – minute
DINT[5] – second
DINT[6] –
sec.
6
Set / SSV
Current UT value
(UTC Time)
LINT
Current value of Wall Clock Time. 64-bit μS value
referenced from 0000 hrs January 1, 1970
7
Set / SSV
UTC Date and Time
(UTC Time)
DINT[7] –
Array of seven DINTs
Current time in human readable format.
DINT[0] – year
DINT[1] – month
DINT[2] – day
DINT[3] – hour
DINT[4] – minute
DINT[5] – second
DINT[6] –
sec.
8
Set / SSV
Time Zone String
Struct of UDINT
SINT[Length]
This string specifies the time zone where the controller is
located, and ultimately the adjustment in hours and minutes
applied to the UTC value to generate the local time value.
TimeZoneString can be specified in the following formats:
o UTC+hh:mm <location>
o UTC-hh:mm <location>
hh:mm portion is used internally to calculate the local time, and
the <location> portion is used to describe the time zone and is
optional.
GMT is also accepted
Length of the Data array can be from 10 to 82.
Examples:
UTC-05:00 Eastern Time
UTC+01:00 Coordinated Universal Time
9
Set / SSV
DST Adjustment
INT
The number of minutes to be adjusted for daylight saving time
10
Set / SSV
Enable DST
USINT
It specifies if we are in daylight saving time or not. Not internally
set. Needs user action.
11
Set
Current value
(local time)
LINT
Adjusted Local value of Wall Clock Time.
64-bit μS value referenced from 0000 hrs January 1, 1970
Attribute ID Access Rule
Name
Data Type
Value
Service Code
Implemented for:
Service Name
Class
Instance
0x0E
Yes
Yes
GetAttributes_All
0x10
Yes
No
Set_Attribute_Single
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......