Analog Module 2 – Input Channel 00 Type
Analog Module 2 – Input Channel 00 Type (Parameter 468) defines the type of
analog signal that Input Channel 00 of Analog Module 2 will be monitoring.
Table 93 - Analog Module 2 – Input Channel 00 Type (Parameter 468)
Analog Module 2 – Input Channel 00 Format
Analog Module 2 – Input Channel 00 Format (Parameter 469) defines the data
format for how the analog reading is reported.
Table 94 - Analog Module 2 – Input Channel 00 Format (Parameter 469)
Analog Module 2 – Input Channel 00 Temperature Unit
Analog Module 2 – Input Channel 00 Temperature Unit (Parameter 470)
defines the temperate unit for RTD sensor readings.
Value
Assignment
Description
0
Disabled
Disable the analog input
1
4To20mA
Read an analog current signal from 4…20 mA
2
0To20mA
Read an analog current signal from 0…20 mA
3
0To10Volts
Read an analog voltage signal from 0…10 V DC
4
1To5Volts
Read an analog voltage signal from 1…5 V DC
5
0To5Volts
Read an analog voltage signal from 0…5 V DC
6
100Pt385
Read a 100 Ω Pt 385 RTD Sensor
7
200Pt385
Read a 200 Ω Pt 385 RTD Sensor
8
500Pt385
Read a 500 Ω Pt 385 RTD Sensor
9
1000Pt385
Read a 1000 Ω Pt 385 RTD Sensor
10
100Pt3916
Read a 100 Ω Pt 3916 RTD Sensor
11
200Pt3916
Read a 200 Ω Pt 3916 RTD Sensor
12
500Pt3916
Read a 500 Ω Pt 3916 RTD Sensor
13
1000Pt3916
Read a 1000 Ω Pt 3916 RTD Sensor
14
10Cu426
Read a 10 Ω Cu 426 RTD Sensor
15
100Ni618
Read a 100 Ω Ni 618 RTD Sensor
16
120Ni672
Read a 120 Ω Ni 672 RTD Sensor
17
604NiFe518
Read a 604Ω NiFe 518 RTD Sensor
18
150ohm
Read a resistance signal from 0…150 Ω
19
750ohm
Read a resistance signal from 0…750 Ω
20
3000ohm
Read a resistance signal from 0…3000 Ω
21
6000ohm
Read a resistance signal from 0…6000 Ω. This
setting can be used with PTC and NTC sensors.
Value
Assignment
Description
0
EngUnits
Engineering Units (mA, V, °C, °F, or Ω)
1
EngUnitsTimes10
Engineering Units x 10 (mA, V, °C, °F, or Ω)
2
RawProportional
Raw / Proportional (-32768 - 32767)
3
ScaledForPID
Scaled for PID (0 - 16383)
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......