Rockwell Automation Publication 193-UM015D-EN-P - February 2015
461
Appendix
B
Parameter List
Overview
This appendix lists all accessible parameters of the E300™ overload relay in
numerical order.
The setting range for each parameter is provided to assist especially for
applications where it is desirable to set values from a logic controller via a network
connection.
Information values provided include the following:
Value
Function
Setting Range
Indicated as raw numerical values.
Scale Factor
Indicate the decimal precision associated with each parameter. This must be given close attention when writing or
reading values.
Default
Indicate the factory pre-programmed values.
Group
Param
No.
Parameter Name
Device Profile Tag Name
Description
Type
Data Size
(bytes)
Scale
Factor
Min
Max
Default Units
Device Monitor
1
ThermUtilizedPct
I.PercentTCU
% Thermal
Capacity Used
USINT
1
1
0
100
0
%
2
OLTimeToTrip
Time until an
overload trip
UINT
2
1
0
9999
0
Second
s
3
OLTimeToReset
Time until OL trip
can be reset
UINT
2
1
0
9999
0
Second
s
4
TripStsCurrent
I.Protection.OverloadTrip
I.Protection.PhaseLossTrip
I.Protection.GroundFaultCurrentTrip
I.Protection.StallTrip
I.Protection.JamTrip
I.Protection.UnderloadTrip
I.Protection.CurrentImbalanceTrip
I.Protection.L1UnderCurrentTrip
I.Protection.L2UnderCurrentTrip
I.Protection.L3UnderCurrentTrip
I.Protection.L1OverCurrentTrip
I.Protection.L2OverCurrentTrip
I.Protection.L3OverCurrentTrip
I.Protection.L1LineLossTrip
I.Protection.L2LineLossTrip
I.Protection.L3LineLossTrip
Trip Status bits for
Current
UINT
2
1
Bit0= OverloadTrip
Bit1= PhaseLossTrip
Bit2= GroundFaultTrip
Bit3= StallTrip
Bit4= JamTrip
Bit5= UnderloadTrip
Bit6= CurrentImbalTrip
Bit7= L1UnderCurrTrip
Bit8= L2UnderCurrTrip
Bit9= L3UnderCurrTrip
Bit10= L1OverCurrenTrip
Bit11= L2OverCurrenTrip
Bit12= L3OverCurrenTrip
Bit13= L1LineLossTrip
Bit14= L2LineLossTrip
Bit15= L3LineLossTrip
0
5
TripStsVoltage
I.Protection.UnderVoltageTrip
I.Protection.OverVoltageTrip
I.Protection.VoltageImbalanceTrip
I.Protection.PhaseRotationMismatchTrip
I.Protection.UnderFrequencyTrip
I.Protection.OverFrequencyTrip
Trip Status bits for
Voltage
UINT
2
1
Bit0= UnderVoltageTrip
Bit1= OvervoltageTrip
Bit2= VoltageUnbalTrip
Bit3= PhaseRotationTrp
Bit4= UnderFreqTrip
Bit5= OverFreqTrip
0
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...