Rockwell Automation Publication 193-UM015D-EN-P - February 2015
505
EtherNet/IP Information
Appendix C
Table 525 - Extended Device Status Field (bits 4-7) in “Status” Instance Attribute 5
Instance 2 of the Identity Object contains the following attributes:
Table 526 - Identity Object Instance 2 Attributes
Value
Description
0
Self-Testing or Unknown
1
Firmware Update in Progress
2
At least one faulted I/O connection
3
No I/O connections established
4
Nonvolatile Configuration bad
5
Major Fault – either bit 10 or bit 11 is true (1)
6
At least one I/O connection in run mode
7
At least one I/O connection established, all in idle mode
Attribute ID
Access Rule
Name
Data Type
Value
1
Get
Vendor
UINT
1 = Allen-Bradley
2
Get
Device Type
UINT
3
3
Get
Product Code
UINT
651
4
Get
Revision
Major Revision
Minor Revision
Structure of:
USINT
USINT
Firmware revision of the Boot Code
5
Get
Status
WORD
Bit 0 – 0=not owned; 1=owned by master
Bit 2 – 0=Factory Defaulted; 1=Configured
Bits 4-7 – Extended Status (see
Bit 8 – Minor Recoverable fault
Bit 9 – Minor Unrecoverable fault
Bit 10 – Major Recoverable fault
Bit 11 – Major Unrecoverable fault
6
Get
Serial Number
UDINT
unique number for each device
7
Get
Product Name
String Length
ASCII String
Structure of:
USINT
STRING
“193-EIO Boot Code”
8
Get
State
USINT
See CIP Common Spec
9
Get
Configuration
Consistency Value
UINT
16 bit CRC or checksum of all data included in the
following data sets:
Parameter included in the configuration assembly
MCC Object configuration data
DeviceLogix program data
Base Energy Object attribute 16
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......