534
Rockwell Automation Publication 193-UM015D-EN-P - February 2015
Appendix C
EtherNet/IP Information
Electrical Energy Object — CLASS CODE 0x004F
No class attributes are supported for the Electrical Energy Object.
A single instance of the Electrical Energy Object is supported
Table 576 - Electrical Energy Object Instance Attributes
11
REAL
Energy Transfer Rate User Setting 0.0
12
STRUCT of UINT,
Padded EPATH
1
Energy Type Specific Object Path
Attribute 12 value
13
UINT
Energy Aggregation Path Array
Size
0
14
Array of STRUCT
of UINT, Padded
EPATH
1
Energy Aggregation Paths
Null
15
STRINGI
Energy Identifier
LanguageChar1 USINT =‘e’
LanguageChar2 USINT)=‘n’
LanguageChar3 USINT) =‘g’
CharStringStruct USINT=0xD0
CharSet UINT = 0 = undefined
InternationalString = null
16
BOOL
Odometer Reset Enable
Attribute 16 value
17
BOOL
Metering State
1
Attribute ID Access Rule
Name
Data Type
Value
1
Get
Real Energy Consumed
Odometer
ODOMETER
Returns params 80-84 values.
3
Get
Real Energy Net
Odometer
SIGNED ODOMEETER
Returns params 80-84 values.
4
Get
Reactive Energy
Consumed Odometer
ODOMETER
Returns params 85-89 values.
5
Get
Reactive Energy
Generated Odometer
ODOMETER
Returns params 90-94 values.
6
Get
Reactive Energy Net
Odometer
SIGNED ODOMETER
Returns params 95-99 values.
7
Get
Apparent Energy
Odometer
ODOMETER
Returns params 100-104 values.
9
Get
Line Frequency
REAL
Param 62 value converted to a REAL
10
Get
L1 Current
REAL
Param 43 value converted to a REAL
11
Get
L2 Current
REAL
Param 44 value converted to a REAL
12
Get
L3 Current
REAL
Param 45 value converted to a REAL
13
Get
Average Current
REAL
Param 46 value converted to a REAL
14
Get
Percent Current
Unbalance
REAL
Param 52 value converted to a REAL
15
Get
L1 to N Voltage
REAL
Param 57 value converted to a REAL
16
Get
L2 to N Voltage
REAL
Param 58 value converted to a REAL
17
Get
L3 to N Voltage
REAL
Param 59 value converted to a REAL
18
Get
Avg Voltage L to N
REAL
Param 60 value converted to a REAL
19
Get
L1 to L2 Voltage
REAL
Param 53 value converted to a REAL
20
Get
L2 to L3 Voltage
REAL
Param 54 value converted to a REAL
21
Get
L3 to L1 Voltage
REAL
Param 55 value converted to a REAL
22
Get
Avg Voltage Lto N
REAL
Param 56 value converted to a REAL
Attribute ID
Data Type
Name
Value
Summary of Contents for Allen-Bradley E300
Page 1: ...E300 Electronic Overload Relay Bul 193 592 User Manual...
Page 128: ...128 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 5 Operating Modes...
Page 304: ...304 Rockwell Automation Publication 193 UM015D EN P February 2015 Chapter 7 Commands Notes...
Page 502: ...502 Rockwell Automation Publication193 UM015D EN P November 2013 Appendix B Parameter List...
Page 545: ......