Rockwell Automation Publication 440R-IN087A-EN-P - July 2022

Minotaur MSR131RTP Monitoring Safety Relay Installation Instructions

Diagnostics

The solid-state status signal Y35 indicates the safety input state. The solid-state 
status output Y32 and the auxiliary (N.C.) output 41-42 signals the safety output 
state.

Safety Input

One safety device can be monitored per unit. According to the wiring inputs, 
cross-loop monitoring of the inputs is enabled or disabled. You can enable cross-
loop monitoring for 2-channel safety inputs in 4-wire connection (S11-S12, S21-S22). 
Cross-loop monitoring is disabled for single-channel inputs, dual-channel inputs in 
3-wire connection, and 24V DC signals. For external 24V DC signals, the negative 
pole must connect to S21.

Reset

Reset modes - The reset mode is configurable for automatic/manual start 
and manual monitored reset (MSR

xxx

RT). 

A valid start/reset can only be operated if the feedback circuit is closed. 
Feedback contacts (N.C.) of controlled actuators connect to Y1-Y2.

T - Automatic/manual start

T = (Jumper X1-X2, X3-X4)

In Automatic/Manual Start mode, the reset circuit S33-S34 is not 
monitored against signal changes (no edge detection). The safety relay is 
active once the safety inputs and the reset circuit close. If the safety 
inputs and reset circuit concurrently close during power-up, the safety 
relay activates immediately.

R - Manual monitored reset
R = (no Jumper)
In Manual Monitored Reset mode, a signal change of the reset circuit 
(S33-S34) is required and monitored. A reset fault occurs if the safety 
inputs remain open while the reset circuit is closed.

-

Positive edge:

The safety relay is active once the safety inputs close and then the 
reset circuit is closed.

-

Negative edge (440R-

xxxxx

M):

The safety relay is active once the safety inputs close and then the 
reset circuit closes and releases again. The circuit resets upon release 
of the Reset button.

For both methods, the MSR131RTP safety relay is suitable for the safety 
requirements according to EN/ISO 13849-1.

Recovery time

100 ms

Impulse withstand voltage

2500V

Pollution degree

2

Installation group

Overvoltage category III, VDE 0110-1

Operating temperature

-5…+55 °C (23…131 °F)

Relative Humidity

90% 

Enclosure protection

IP40 (NEMA 1)

Terminal protection

IP20

Wiring

Use copper that withstands 60/75 °C (140/167 °F)

Conductor size

0.2...2.5 mm

2

 (24…12 AWG)

Torque settings

Terminal screws: 0.6…0.8 N•m (5…7 lb•in)

Case material

Polyamide PA 6.6

Mounting

35 mm (1.38 in.) DIN rail in enclosure to a minimum of IP54

Weight

24V AC/DC: 320 g (0.71 lb)
115V AC or 230V AC: 450 g (0.99 lb)

Vibration

10…55 Hz, 0.35 mm (0.01 in.)

(1)

Operation time (day, hour)

(2)

Cycle time (hour, sec)

Max PLc: 1-CH 

(1)

; N.C.

(1)

1-CH = Single-channel

Max PLd: 2-CH 

(2)

; 3-wire connection

(2)

2-CH = Dual-channel

Max PLe: 2-CH 

(2)

; 24V DC signal

Max PLe: 2-CH 

(2)

; 4-wire connection, cross 

faults require fault reset

Table 1 - Technical Specifications  (Continued)

Attribute

Value

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S12

S11

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S12

S11

MSR

xxx

T

MSR

xxx

R

440R-

xxxxx

M

S12

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S11

S12

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S11

MSR

xxx

R

MSR

xxx

R

440R-

xxxxx

M

K2

K1

S12

X3

X1

Y1

X4

X2

Y2

S34

S33

S11

MSR

xxx

R

Reviews: