Rockwell Automation Publication 2071-UM001E-EN-P - November 2013
89
Configure Your Drive for Communication
Chapter 6
To configure the Kinetix 3 drive communication port for RS-232/ASCII
communication follow these steps.
1.
Use the keypad on the front of the drive to set the following parameters.
for keypad operation.
2.
Connect to your personal computer with the RS-232 serial
communication cable, catalog number 2090-CCMPCDS-23AA
xx.
For information on the serial communication cables, refer to Serial
Communication Cables Installation Instructions,
publication
3.
, Using Ultraware Software to Configure the
Drive, on
Parameter Name
Parameter
Setting
Drive Address
Pr0.07
Required address (1 - Default)
Serial Port Configuration
Pr0.09
0005 - Default
where,
5 - 57,600 Kbps Baud Rate
0 - 8 Data Bits, No Parity, 1 Stop Bit
0 - ASCII protocol
0 - RS-232
3
2
1
Item
Description
1
Kinetix 3 drive
2
RS-232 serial communication cable, catalog number 2090-CCMPCDS-23AA
3
Personal computer with Ultraware software