Chapter 4
Connect the Kinetix 3 Drive
Three-phase Power Wired to Single-phase Drives
This example illustrates grounded three-phase power wired to single-phase
Kinetix 3 drives when phase-to-phase voltage is within drive specifications. The
optional grounded neutral is omitted on ungrounded systems.
Figure 27 - Single-phase Amplifiers on Three-phase Power (WYE)
(1) AC line filter is optional, but is required for CE compliance.
Feeder short circuit protection is not illustrated.
If a three-phase line filter is used to feed multiple single-phase drives (not
recommended), it is important that the filter include a neutral connection as
shown above. This applies if three-phase is brought directly into the filter and no
isolating transformer is present.
L1
L2
L3
L1
L2
L3
L2
L3
L1
L1
L2
L1
L2
E
L1
L2
L1
L2
E
L1
L2
L1
L2
E
IPD
L1
L2
L3
LC1
LC2
IPD
L1
L2
L3
LC1
LC2
IPD
L1
L2
L3
LC1
LC2
Bonded Cabinet Ground
Bus
Transformer
(WYE) Secondary
Grounded Neutral
(optional)
Ground Grid or
Power Distribution Ground
Bonded Cabinet Ground
Bus
Ground Grid or
Power Distribution Ground
AC Line
Filter
(1)
Kinetix 3 Drive
(System A)
Single-phase AC Input
IDP Terminals
Kinetix 3 Drive
(System B)
Single-phase AC Input
IDP Terminals
Kinetix 3 Drive
(System C)
Single-phase AC Input
IDP Terminals
AC Line
Filter
(1)
AC Line
Filter
(1)
Summary of Contents for Allen-Bradley Kinetix 3 2071-A10
Page 4: ...4 Rockwell Automation Publication 2071 UM001E EN P November 2013 Summary of Changes Notes ...
Page 8: ...8 Rockwell Automation Publication 2071 UM001E EN P November 2013 Table of Contents Notes ...
Page 16: ...16 Rockwell Automation Publication 2071 UM001E EN P November 2013 Chapter 1 Start Notes ...